Version 3.11 | HPI Combi Flow User Guide | 55www.lafert.com
Par. Parameter Name Units
P0-40 Motor Current Log (256ms) Amps
Diagnostic log for Motor Current. Values logged every 256ms with 8 samples total. Logging suspended on drive trip.
NOTE The above parameters (P0-36 to P0-40) are used to store the history of various measured levels within the drive at various regular time
intervals prior to a trip. The values are frozen when a fault occurs and can be used for diagnostic purposes.
P0-41 Over Current Fault Counter -
P0-42 Over Voltage Fault Counter -
P0-43 Under Voltage Fault Counter -
P0-44 Heatsink Over Temperature Fault Counter -
P0-45 Reserved -
P0-46 Ambient Over Temperature Fault Counter -
NOTE These parameters (P0-41 to P0-46) contain a record of how many times certain critical faults have occurred during a drives operating
lifetime. This provides useful diagnostic data.
P0-47 I/O Comms Fault Counter -
Displays the number of communication errors detected by the I/O processor in messages received from the power stage processor
since the last power up.
P0-48 DSP Comms Fault Counter -
Displays the number of communication errors detected by the Power Stage processor in messages received from the I/O processor
since the last power up.
P0-49 Modbus RTU / BACnet MSTP Fault Counter -
This parameter is incremented every time an error occurs on the Modbus RTU communication link. This information can be used for
diagnostic purposes.
9
Extended Parameters