- 62 -
When the remote display is set to gross weight:
- if the instrument displays the gross weight, the remote display shows the gross weight.
- if the instrument shows the net weight, the remote display shows the net weight alternated
with the message .
- : transmission speed (2400, 4800, 9600, 19200, 38400, 115200; default: 9600).
- : instrument address (from 1 to 99; default: 1).
- : maximum transmission frequency (10 20 30 40 50 60 70 80 100
200 300; default: 10); to be set when the  transmission protocol is selected.
Maximum setting frequency ():
- 20 Hz with minimum baud rate 2400 baud.
- 40 Hz with minimum baud rate 4800 baud.
- 80 Hz with minimum baud rate 9600 baud.
- 100 Hz with minimum baud rate 19200 baud.
- 200 Hz with minimum baud rate 38400 baud.
- 300 Hz with minimum baud rate 38400 baud.
- : delay in milliseconds which elapses before the instrument replies (from 0 to
200 ms; default: 0).
- :
- : no parity (default).
- : even parity.
- : odd parity.
- : stop bit (1 2; default: 1).
FAST CONTINUOUS TRANSMISSION PROTOCOL
This protocol allows the continuous transmission of the weight at high update frequencies. Up to 300
strings per second are transmitted with a minimum transmission rate of 38400 baud.
Following communication modes availables (see section SERIAL COMMUNICATION SETTINGS):
: communication compatible with TX RS485 instruments.
: communication compatible with TD RS485 instruments.
If  is set, the following string is transmitted to PC/PLC:
xxxxxxCRLF
where: xxxxxx ...... 6 characters of gross weight (48
57 ASCII)
CR ................ 1 character return to the start (13 ASCII)
LF ................ 1 character on new line (10 ASCII)