4.5.6 Network Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
P400
Network
Protocol
0 Not Active This parameter will only display
the selection for the module that is
installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Probus
7 Lecom-B
8 I/O Module
P401
Module Type
Installed
0 0 No Module Installed Module type format: 0xAABC; Drive
Display: AA.B.C
AA = Module Type
B = Major revision
C = minor revision
1 Basic I/O (0x0100, 1.0.0)
2 RS485/Rem. Keypad
(0x0200, 2.0.0)
3 CANopen (0x0300, 3.0.0)
11 PROFIBUS (0x1100, 11.0.0)
12 Ethernet (0x1200, 12.0.0)
P402
Module Status 0 0 Not Initialized
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed Module type mismatch P401
7 Initialization Error Protocol selection mismatch P400
P403
Module Reset 0 0 No Action
Returns module parameters 401…499
to the default values shown in the
manual
1 Reset parameters to default
values
P404
Module Timeout
Action
0 0 No Fault Action to be taken in the event of a
Module/Drive Time-out.
Time is xed at 200ms
STOP is by the method selected in
P111.
1 STOP (see P111)
2 Quick Stop
3 Fault (F_ntF)