Commissioning
4.5.9.1 Sequencer Parameters
WARNING
If the input dened to “Start Sequence” is opened during a sequence, the
drive will exit sequencer mode and will run at the specied standard or
alternate speed source (dependent on drive conguration).
Drive Stop/Start Control
TB-13C
TB-13B
TB-13A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
P701
P702
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
P703
P121
24
P122
24
P123
24
3
2
3
P700
0
2
Sequencer
mode
disabled
1
Start
Segment
Start
Segment
Start
Segment
“Start Segment” number selection
WARNING
If none of the digital inputs (TB-13A,B,C or D) are asserted
but a start signal is given from the Start/Stop source (P100)
then the drive will run at the output frequency value governed by
the frequency reference source (P101).
Start from
Local Keypad
Start from
Terminal Strip
0
1
2
(2)
P100
Start from
Remote Keypad
3
(1)
Start from Network
(SMV communications
module)
Notes
(1)
Refer to relevant communications module user guide for starting from a
communications network, RS485 etc..
(2)
Refer to P100 description in the SMV Operating instructions for further
combinations of start sources.
> Selections shown as default values
Digital Input priority:
TB-13A -Lowest
TB-13B
TB-13C
Sequencer Flow Diagram
TB-13D
24
P124
P704
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Segment
Start
TB-13D - Highest
(3)
TB-13D available on SMV models rated 15HP (11kW) or greater.
(3)
Notes
(1) Refer to relevant communications module user guide for
starting from a communications network, RS485 etc.
(2) Refer to P100 description in the Operating instructions for
further combinations of start sources.
(3) TB-13D available on models rated 15HP (11kW) or greater.
> Selections shown as default values
CALL NOW 800-985-6929
http://www.automatedpt.com
Email: charles@automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Email: charles@automatedpt.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Leeson SPEEDMASTER SM2 Series and is the answer not in the manual?

Leeson SPEEDMASTER SM2 Series Specifications

General IconGeneral
BrandLeeson
ModelSPEEDMASTER SM2 Series
CategoryDC Drives
LanguageEnglish

Related product manuals