PARAMETER SETTING DISPLAY
BUZZER
(this setting can’t be
changed with this
procedure)
ON
OFF
BATTERY TEST
(this setting can’t be
changed with this
procedure)
OFF
BYPASS VOLTAGE
RANGE
LOW
The bypass voltage range
is set to ±15% of the
selected output voltage
HIGH
The bypass voltage range
is set to ±10% of the
selected output voltage
BYPASS
FREQUENCY
RANGE
± 1 Hz
± 3 Hz
If during the normal
functioning the bypass
frequency goes beyond
the setting, the UPS turns
to stored energy mode
OUTPUT
VOLTAGE
200 V
208 V
220 V
230 V
240 V
4 Operation