II – Enclosure:
Casing:
o Protection index: IP 30
o Mechanical impact resistance: IK 10
o Enclosure colour: RAL 7035 + black base
(1)
Generator set contact terminal blocks: YES
(2)
CT secondary connection contact terminal blocks: YES
(2)
Contact terminal blocks + smoke detector safety kit: YES
(2)(3)
III – ALPIVAR capacitors:
Capacitance tolerance: ± 5%
Permissible overvoltage: 1.18 x Un (12/24 hrs)
Conformity with standards: IEC 60831-1/2
Loss factor: 0.3 W/kVAr (this consumption value includes the discharge resistors)
IV – Ranges:
THDu: voltage total harmonic distortion
THDi: current total harmonic distortion
SH: expanded power of the harmonic generators in the secondary of the MV/LV
transformer to be compensated (in kVA)
ST: transformer power (in kVA)
(1)
Except on enclosures with power ≤ 125 kVAr.
(2)
See connection/auxiliary circuits section on page 38 for more information.
(3)
Not included in 770 mm high enclosures without reactors, in version with circuit breaker with power ≤ 125 kVAr, in version
without circuit breaker with power ≤ 150 kVAr.
(4)
Enclosure with detuned reactor, check the frequency is compatible with your electricity supplier. For other frequencies, please
consult your Legrand Group representative.
(5)
Above this harmonic level, please contact your Legrand Group representative who can do an audit of the installation and offer
you a bespoke solution to meet your requirements (compensation, harmonic processing).