Page 3
SPECIFICATIONS
General
Data
Model No. 13HPX−042 13HPX−048 13HPX−060 13HPX−061
Nominal Tonnage 3.5 4 5 5
1
Sound Rating Number 80 80 80 80
Connections
(sweat)
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
Vapor line o.d. − in. 7/8 7/8 1-1/8 1-1/8
2
Refrigerant R−410A charge furnished 10 lbs. 10 oz. 13 lbs. 2 oz. 15 lbs. 3 oz. 15 lbs. 9 oz.
Outdoor
Coil
Net face area
sq. ft.
Outer coil 18.66 21.11 24.50 29.09
Inner coil 17.95 20.31 23.56 28.16
Tube diameter − in. 5/16 5/16 5/16 5/16
No. of rows 2 2 2 2
Fins per inch 22 22 22 22
Outdoor
Fan
Diameter in. 22 22 22 26
No. of Blades 4 4 4 4
Motor hp 1/3 1/3 1/4 1/3
Cfm 3890 3890 3830 45500
Rpm 1080 1085 825 830
Watts 400 375 330 307
Shipping Data − lbs. 1 package 220 250 255 298
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 208/230V 208/230V 208/230V
3
Maximum overcurrent protection (amps) 40 50 60 60
4
Minimum circuit ampacity 24.1 28.9 34.6 34.6
Compressor
Rated Load Amps
17.9 21.8 26.3 26.3
Locked Rotor Amps
112 117 134 134
Power Factor
0.94 0.95 0.98 0.98
Outdoor
Fan Motor
Full Load Amps
1.7 1.7 1.7 1.8
Locked Rotor Amps
4.1 4.1 3.1 2.9
OPTIONAL ACCESSORIES − must be ordered extra
Compressor Crankcase Heater Factory S S S S
Compressor Hard Start Kit 88M91 S S S S
Compressor Low Ambient Cut−Off 45F08 S S S S
Compressor Sound Cover 69J03 S S S S
Freezestat
3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
Hail Guards
12W21 S
92M90 S
92M94 S
94M94 S
5
Low Ambient Kit 54M89 S S S S
Low Pressure Switch Bypass Thermostat 13W07 S S S S
Mild Weather Kit 33M07 S S S S
Monitor Kit − Service Light 76F53 S S S S
Mounting Base 69J07 S S S S
Outdoor Ther-
mostat Kit
Thermostat 56A87 S S S S
Mounting Box 31461 S S S S
Refrigerant
Line Sets
L15−65−30 L15−65−40
L15−65−50
S S
Field Fabricate S S
Time Delay Relay Kit 58M81 S S S S
Unit Stand−Off Kit 94J45 S S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Crankcase Heater and Freezestat are recommended with Low Ambient Kit.

Related product manuals