CLIMATIC™ 60 AIRCOOLED CHILLERS
Page 68 MUL41E-0610/06-2011
Level 1 Item Level 2 Item Level 3 Item Level 4 Item R/W/Z Unit Min Std Max Description
Expert Link 3820 BMS 3821 Status R * * * * Status of the BMS
Expert Link BMS 3822 Outside R °C -50,0 * 105,0 Outside air BMS T°
Expert Link BMS 3823 Inlet R °C -50,0 * 105,0 Evaporator inlet BMS
Expert Link BMS 3824 Outlet R °C -50,0 * 105,0 Evaporator outlet BMS T°
Expert Link BMS 3825 Watchdog R/W * 0 * 32000 Watchdog timer
Expert Link BMS 3826 Id R/W * 1 * 199
Identification number
configuration
Expert Link BMS 3827 Protocol R/W *
0=Adalink,
1=Lnx Vision,
2=Modbus,
3=Trend,
4=Carel,
5=Bacnet,
6=Lon works.
BMS protocol configuration
Expert Link BMS 3828 Bauderate R/W * 0=1200, 1=2400, 2=4800, 3=9600, 4=19200. BMS bauderate configuration
Expert Link BMS 3829 Inoc R/W * 0 * 1 *