Energence
®
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
30 KW - LCH102H4B (1ST STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
18.3°C 23.9°C 29.4°C 35°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
17.2°C
1285 13.8 1.79 0.64 0.82 1 13 2.03 0.65 0.85 1 12.2 2.29 0.66 0.89 1 11.3 2.59 0.67 0.93 1
1605 14.5 1.8 0.7 0.97 1 13.7 2.04 0.71 0.99 1 12.9 2.3 0.72 1 1 12.1 2.6 0.76 1 1
1925 15.2 1.81 0.77 1 1 14.4 2.04 0.79 1 1 13.6 2.3 0.83 1 1 12.8 2.6 0.88 1 1
19.4°C
1285 14.7 1.8 0.5 0.63 0.77 13.9 2.04 0.5 0.63 0.79 13.1 2.3 0.51 0.65 0.83 12.1 2.6 0.51 0.66 0.87
1605 15.4 1.81 0.54 0.68 0.91 14.5 2.04 0.54 0.69 0.95 13.6 2.3 0.54 0.7 0.98 12.7 2.6 0.55 0.72 1
1925 15.9 1.81 0.56 0.74 1 15 2.05 0.57 0.77 1 14.1 2.31 0.57 0.8 1 13.1 2.6 0.59 0.86 1
21.7°C
1285 15.6 1.81 0.38 0.49 0.61 14.7 2.04 0.37 0.49 0.61 13.9 2.3 0.37 0.5 0.63 13 2.6 0.37 0.5 0.64
1605 16.3 1.82 0.4 0.53 0.66 15.4 2.05 0.39 0.54 0.68 14.5 2.31 0.38 0.54 0.68 13.5 2.6 0.38 0.55 0.71
1925 16.8 1.82 0.41 0.56 0.71 15.9 2.05 0.41 0.57 0.74 14.9 2.31 0.4 0.58 0.76 13.9 2.61 0.4 0.58 0.82
30 KW - LCH102H4B (2ND STAGE)
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
26.7°C 35°C 43.3°C 46°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
17.2°C
1285 26.1 4.32 0.73 0.91 1 23.5 5.19 0.75 0.95 1 20.7 6.27 0.77 1 1 20.4 6.89 .81 1.00 1.00
1605 27.5 4.33 0.79 1 1 25.1 5.2 0.83 1 1 22.4 6.27 0.88 1 1 22.1 6.86 .92 1.00 1.00
1925 29 4.34 0.87 1 1 26.4 5.2 0.92 1 1 23.7 6.28 0.98 1 1 23.4 6.83 1.00 1.00 1.00
19.4°C
1285 27.9 4.33 0.57 0.71 0.87 25.2 5.2 0.57 0.73 0.91 22.2 6.27 0.57 0.75 0.96 21.7 6.87 .59 .81 .95
1605 29.1 4.34 0.61 0.78 0.98 26.3 5.2 0.61 0.8 1 23.2 6.27 0.62 0.85 1 22.7 6.84 .65 .91 1.00
1925 30 4.35 0.64 0.85 1 27.1 5.21 0.66 0.9 1 24 6.28 0.68 0.96 1 23.4 6.82 .72 1.00 1.00
21.7°C
1285 29.6 4.34 0.41 0.56 0.69 26.8 5.21 0.41 0.56 0.71 23.8 6.27 0.39 0.56 0.73 23.4 6.83 .40 .59 .73
1605 30.9 4.35 0.43 0.6 0.76 28 5.21 0.42 0.61 0.79 24.8 6.27 0.42 0.62 0.82 24.4 6.81 .43 .66 .82
1925 31.9 4.36 0.45 0.64 0.83 28.8 5.22 0.45 0.65 0.87 25.6 6.28 0.45 0.68 0.94 25.1 6.80 .46 .73 .91
Entering
Wet
Bulb
Temper-
ature
Total
Air
Volume
Outdoor Air Temperature Entering Outdoor Coil
48°C 50°C 51.7°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb Dry Bulb Dry Bulb
L/s kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C kW kW 24°C 27°C 29°C
17.2°C
1285 19.5 7.25 0.79 1 1 18.8 7.65 0.80 1 1 18.1 7.63 0.82 1 1
1605 21.2 7.20 0.91 1 1 20.5 7.58 0.93 1 1 19.5 7.61 0.96 1 1
1925 22.5 7.18 1 1 1 21.7 7.55 1.00 1 1 20.7 7.62 1 1 1
19.4°C
1285 20.9 7.23 0.57 0.76 0.99 20.1 7.61 0.57 0.78 1.00 19.1 7.62 0.58 0.8 1
1605 21.9 7.19 0.63 0.88 1.00 21.1 7.58 0.64 0.90 1.00 20 7.62 0.65 0.93 1
1925 22.6 7.18 0.69 0.98 1.00 21.7 7.53 0.70 1.00 1.00 20.6 7.61 0.71 1 1
21.7°C
1285 22.5 7.18 0.38 0.56 0.74 21.7 7.56 0.37 0.57 0.75 20.5 7.61 0.38 0.58 0.78
1605 23.5 7.16 0.41 0.62 0.85 22.7 7.51 0.40 0.63 0.87 21.5 7.61 0.41 0.65 0.9
1925 24.2 7.16 0.44 0.69 0.96 23.4 7.52 0.44 0.70 0.98 22 7.61 0.44 0.72 1