• 47 •
020-185
3~400V-50Hz 3~342-462V-50Hz
PE L1 L2
L3
GAC/GAH 020 - 185
3 ~ 400V-50Hz + PE
20SM1M 4G x 4 mm² 4G x 6 mm² 4G x 6 mm² 4G x 10 mm²
25SM1M 4G x 6 mm² 4G x 10 mm² 4G x 6 mm² 4G x 10 mm²
30SM1M 4G x 6 mm² 4G x 10 mm² 4G x 10 mm² 4G x 16 mm²
35SM1M 4G x 6 mm² 4G x 10 mm² 4G x 10 mm² 4G x 16 mm²
40SM1M 4G x 6 mm² 4G x 10 mm² 4G x 10 mm² 4G x 16 mm²
45SM1M 4G x 6 mm² 4G x 16 mm² 4G x 10 mm² 4G x 16 mm²
55SM1M 4G x 10 mm²
3 x 25 mm²
1 x 16 mm²
4G x 16 mm²
3 x 35 mm²
1 x 16 mm²
60SM1M 4G x 16 mm²
3 x 25 mm²
1 x 16 mm²
4G x 16 mm²
3 x 50 mm²
1 x 25 mm²
70SM1M 4G x 16 mm²
3 x 35 mm²
1 x 16 mm²
3 x 25 mm²
1 x 16 mm²
3 x 50 mm²
1 x 25 mm²
80SM1M 4G x 16 mm²
3 x 35 mm²
1 x 16 mm²
3 x 35 mm²
1 x 16 mm²
3 x 50 mm²
1 x 25 mm²
90SM1M
3 x 25 mm²
1 x 16 mm²
3 x 50 mm²
1 x 25 mm²
3 x 35 mm²
1 x 16 mm²
3 x 70 mm²
1 x 35 mm²
110SM1M
3 x 35 mm²
1 x 16 mm²
3 x 70 mm²
1 x 35 mm²
3 x 50 mm²
1 x 25 mm²
3 x 95 mm²
1 x 50 mm²
125SM1M
3 x 35 mm²
1 x 16 mm²
3 x 70 mm²
1 x 35 mm²
3 x 70 mm²
1 x 35 mm²
3 x 95 mm²
1 x 50 mm²
110DM1M
3 x 35 mm²
1 x 16 mm²
3 x 70 mm²
1 x 35 mm²
3 x 50 mm²
1 x 25 mm²
3 x 95 mm²
1 x 50 mm²
125DM1M
3 x 50 mm²
1 x 25 mm²
3 x 70 mm²
1 x 35 mm²
3 x 70 mm²
1 x 35 mm²
3 x 120 mm²
1 x 70 mm²
140DM1M
3 x 50 mm²
1 x 25 mm²
3 x 95 mm²
1 x 50 mm²
3 x 70 mm²
1 x 35 mm²
3 x 150 mm²
1 x 95 mm²
160DM1M
3 x 70 mm²
1 x 35 mm²
3 x 95 mm²
1 x 50 mm²
3 x 95 mm²
1 x 50 mm²
3 x 150 mm²
1 x 95 mm²
185DM1M
3 x 70 mm²
1 x 35 mm²
3 x 120 mm²
1 x 70 mm²
3 x 120 mm²
1 x 70 mm²
3 x 185 mm²
1 x 95 mm²
Installation manual /eCOMFORT
-MIL150E-0916 / 05/2017
2.8.-ELECTRICAL CONNECTIONS
- BEFORE MAKING ANY ELECTRICAL CONNECTIONS, BE SURE THAT ALL CIRCUIT BREAKERS ARE OPEN AND SUPPLY IS
OFF.
- IN ORDER TO CARRY OUT THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE
UNIT.
- WTHH: Water tank electrical heater
- The cable sections have been calculated based on.
• A distance of 50m and variation of -10V.
• XLPE insulation cupper cable over perforated cable tray.
• Max. Tª: 50ºC
• Type of cable in Cu RV-K.
- Do not start the unit if the drop is greater than this.
- The wiring and circuit breakers to be mounted in the installation must comply with the Regulations in force.
- Ground wires must be properly connected and have a greater length than the phase wires.
VOLTAGE OPERATION LIMITS
MODELS VOLTAGE LIMITS
2.- INSTALLATION
POWER SUPPLY UNIT MODEL
NUMBER OF WIRE x SECTION
COBRE / CUPPER
CU
ALUMINIO / ALUMINIUN
AL
WITHOUT WTHH WITH WTHH WITHOUT WTHH WITH WTHH