18
Table 5. Advanced Settings
MENU SETTING (default is bold) Notes:
SMOOTH SETBACK RECOVERY Enabled or Disabled
When enabled, smooth set back begins
recovery up to two hours before the
programmed time so that the programmed
temperature is reached at the corresponding
programmed event time. Assume 12°F
(6.72°C) per hour for rst-stage gas/electric
heating and 6°F (3.36°C) per hour for rst-
stage compressor based heating or cooling.
With Smooth Set Back disabled, the system
will start a recovery at the programmed time.
Options are enabled or disabled. Default is
enabled.
OFFSET
Temperature Offset - 0°F Adjustable (-5 to 5°F)
Humidity Offset - 0% Adjustable (-10 to 10%)
STAGE DIFFERENTIAL
Stage 1 - 1.0°F Adjustable (0.5 to 8.0°F)
Stage 2 - 1.0°F Adjustable (0.5 to 8.0°F)
Stage 3 - 0.5°F Adjustable (0.5 to 8.0°F)
Stage 4 - 0.5°F Adjustable (0.5 to 8.0°F)
STAGE DELAY
On or O󰀨
Stage 2 through 4 - 20 min.
Adjustable (5 to 120 minutes). Default is 20
min.
H/C STAGES LOCKED IN Enable or Disable Turns heating stages off separately