Table 5. Advanced Settings
MENU SETTING (default is bold) Notes:
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to ENABLED
Fresh Air Damper Ventilation CFM
Default is 75 CFM. Range is 20 to
250 CFM
STAGE 2 HP LOCK TEMP O 󰀨 , 40°F, 45°F, 50°F, 55°F
Heat Pump - for dual-fuel applications (locks
out 2nd stage compressor)
COMPRESSOR PROTECT On or O󰀨
This feature prevents the compressor from
being short cycled any time the compressor is
turned “OFF”.
DISPLAY PERFORMANCE REPORT On or O󰀨
TERMINAL SETTINGS
H/D
Off
Humidify
Dehumidify
ACC
O󰀨
Humidify
Dehumidify
Ventilation
O/B
O (energized during cooling)
B (energized during heating)
SYSTEM TEST MODE Conrm Button
Installer run tests to check all output relays.
Tests conrm signals between thermostat/unit
are being sent/received. Stops system to run
system tests
RESET SETTING Conrm Button Resets all parameters to factory settings
RESTART Conrm Button Reboot the thermostat.