20
Table 5. Advanced Settings
MENU SETTING (default is bold) Notes:
VENTILATION SETTINGS
Ventilator Type: Fresh Air Damper
VENTILATION CONTROL MODE (VCM): ASHRAE or Timed
VCM = TIMED
Relay Setting to Work Fresh Air Damper Closed or Open. Default is Closed.
Ventilation Minutes Per Hour Default is 20 minutes. Range is 0 to 60 minutes
Ventilation High Outdoor Temperature Limit Default is 100⁰F. Range is 60⁰F to 115⁰F.
Ventilation Low Outdoor Temperature Limit Default is 0⁰F. Range is -20⁰F to 55⁰ F.
Ventilation High Outdoor Dew Point Limit Default is 55⁰F. Range is 45⁰F to 80⁰F.
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to DISABLED.
Relay Setting to Work Fresh Air Damper Closed or Open. Default is Closed.
ASHRAE Compliance Check
YES or No: Current settings comply with
ASHRAE 62.2.
ASHRAE Inltration Credit Default is 0 CFM. Range is 0 to 200 CFM.
ASHRAE house oor area serviced by this
ventilator
Default is 2500 square feet. Range is 500 to
5000 square feet.
ASHRAE Number of Bedrooms Default is 3. Range is 1 to 10.
Fresh Air Damper Ventilation CFM Default is 75 CFM. Range is 20 to 250 CFM.
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to ENABLED.
Ventilation High Outdoor Temperature Limit Default is 100⁰F. Range is 60⁰F to 115⁰F.
Ventilation Low Outdoor Temperature Limit Default is 0⁰F. Range is -20⁰F to 55⁰ F.
Ventilation High Outdoor Dew Point Limit Default is 55⁰F. Range is 45⁰F to 80⁰F.
ASHRAE Compliance Check
YES or No: Current settings comply with
ASHRAE 62.2.
ASHRAE Inltration Credit Default is 0 CFM. Range is 0 to 200 CFM.
ASHRAE house oor area serviced by this
ventilator
Default is 2500 square feet. Range is 500 to
5000 square feet.
ASHRAE Number of Bedrooms Default is 3. Range is 1 to 10.