36
Table 7. Alert Codes and Troubleshooting
Alert
Code
Priority Condition
Actual Displayed
Alert Text Under
dealer control center
> Notications
Component or System Operational
State and Troubleshooting Tip
How to clear
alert code
180 Service Soon
Outdoor Temperature
Sensor Problem
The thermostat has found a problem with the outdoor
temperature sensor. In normal operation after system
component control recognizes sensors, the alert code
will be sent if valid temperature reading is lost.
• Compare outdoor sensor resistance to
temperature / resistance charts in unit installation
instructions. Replace sensors pack if necessary.
• At the beginning of (any) conguration, furnace,
air-handler control or equipment interface module
will detect the presence of the sensor(s).
• If detected (reading in range), appropriate feature
will be set as ‘installed’ and shown in the ‘About’
screen.
Automatically clears upon
conguration, or sensing
normal values.
610 Service Urgent
Low Room
Temperature
Detected
This alert will automatically notied the user that a low
room temperature condition exist. A notication is dis-
played on the HD display and email notication sent
to homeowner and dealer.
The freeze alert protection parameter range is 30°F to
50°F (-1.11 to 10.0°C). Default is 40°F (4.44°C).
NOTE: Notication is dependent on
the thermostat having a active
Wi-Fi connection and the user
account has been setup and
includes a valid email address.
Automatically clears when
condition is resolved.