51
Installation and Maintenance
Service Manual
9.2 Error Code List
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor
Unit
(Indicator has 3 kinds of
display status and they
will be displayed circularly
every 5s.)
A/C Status Possible Causes Countermeasures
Display
of dual-
8 nixie
tube
Indicator Display (during
blinking, ON 0.5s and OFF
0.5s)
□OFF
■Illuminated
Blink
Operation
Indicator
Cool
Indicator
Heat
Indicator
D40/
D5
D41/
D6
D42/
D16
D43/
D30
1
High
pressure
protection
E1
Flash
once
every 3s
During
cooling
and drying
operation,
compressor
and outdoor
fan stop while
indoor fan
operates.
During
heating
operation, all
loads stop.
Refrigerant is
superabundant;
1. Reduce
refrigerant volume;
Poor heat-
exchanging
(including heat
exchanger is dirty
and radiating
environment is
not good);
2. Clean the
heat exchanger;
improve radiating
environment of
unit;
Ambient
temperature is
too high;
3. Reduce load
Poor connection
of LPP;
4. After de-
energization,
reinsert LPP
terminal tightly;
Pressure switch
is damaged;
5. Replace
pressure switch;
Hardware
malfunction of
outdoor unit's
main board;
6. Replace outdoor
unit's main board;
2
Freeze
protection
E2
Flash
twice
every 3s
During
cooling
and drying
operation,
compressor
and outdoor
fan stop while
indoor fan
operates.
During
heating
operation, all
loads stop.
Poor air return of
indoor unit;
1. Check
whether indoor
unit's horizontal
louver can close
normally;
Rotation speed
of indoor fan is
abnormal;
2. Replace indoor
unit's main board→
replace indoor fan
Evaporator is
dirty;
3. Clean
evaporator of
indoor unit;