Page 105
Table 64. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.Parameter Short DescriptionScreen Name
31 BLOWER PID P CONST
Blower Proportional Base
Control Loop for Variable Air
Volume or Constant Air Volume
with Bypass Damper
0 17 127 Counts
Variable Air Volume or Constant Air Volume with Bypass Damper
supply PID Proportional constant.
32 BLOWER PID I CONST
Blower Integral Base Control
Loop for Variable Air Volume or
Constant Air Volume with
Bypass Damper
0 12 127 Counts
Variable Air Volume or Constant Air Volume with Bypass Damper
supply PID Integral constant.
33 BLOWR PID D CONST
Blower Derivative Base Control
Loop for Variable Air Volume or
Constant Air Volume with
Bypass Damper
0 0 127 Counts
Variable Air Volume or Constant Air Volume with Bypass Damper
supply PID derivative constant.
34 BLR STC PRESS SMK SP
Constant Air Volume with
Bypass Damper Static Pressure
Setpoint During Smoke Alarm
0 1 5 w.c.
Constant air volume with bypass damper static pressure set point
during smoke alarm.
35 BLR STC PRES VT SP
Constant Air Volume with
Bypass Damper Static Pressure
Setpoint for Ventilation
0 1 5 w.c.
Constant air volume with bypass damper static pressure set point for
ventilation.
36 BLR STC PRES HT SP
Constant Air Volume with
Bypass Damper Static Pressure
Setpoint for Heating
0 1 5 w.c.
Constant air volume with bypass damper static pressure set point for
heating
37 BLR STC PRES CL SP
Constant Air Volume with
Bypass Damper Static Pressure
Setpoint for Cooling
0 1 5 w.c.
Constant air volume with bypass damper static pressure set point for
cooling
38
MIN OUTPT CL VT SMK
Constant Air Volume with
Bypass Damper Minimum
Output Percentage Setpoint for
Cooling, Ventilation and Smoke
Alarms
20.0 20.0 100.0 %
Constant air volume with bypass damper minimum output for
cooling, ventilation and during smoke alarms. This sets the minim
um air delivered.
Bypass damper motor is set to 10 to 2 volts with 10 volts being
closed.
20% setting = 2 volts or damper completely opened.
39
MIN OUTPUT HEAT
Constant Air Volume with
Bypass Damper Minimum
Output Percentage Setpoint for
Heating
20.0 20.0 100.0 %
Constant air volume with bypass damper minimum output for
heating.
This sets the minimum air delivered.
Bypass damper motor is set to 10 to 2 volts with 10 volts being
closed.
20% setting = 2 volts or damper completely opened.
40 BLOWER MAX OUTPUT
Constant Air Volume with
Bypass Damper Maximum
Output Percentage Setpoint
40.0 100.0 100.0 %
Constant air volume with bypass damper maximum output.
This sets the maximum air delivered.
Bypass damper motor is set to 10 to 2 volts with 10 volts being
closed.
100% setting = 10 volts or damper completely closed.