Table 58. Menu Interface (Level 1 - SETUP)
Level 2 Level 3 Level 4 Level 5 Level 6
INSTALL
LANGUAGE = = ENGLISH, ESPANOL, OR FRANCAIS
DATE/TIME = = DAY, MONTH, YEAR, HOURS, MINUTES, SECONDS
DISPLAY UNITS F/C = FAHRENHEIT OR CELSIUS
MODEL NUMBER = LOCATED ON UNIT NAMEPLATE.
CONFIGURATION ID 1
SEE WHITE STICKER TITLED “ORIGINAL FACTORY UNIT CONFIGURATION” LOCATED ON
THE RIGHT SIDE OF THE CONTROL BOX NEAR THE M3 CONTROLLER.
CONFIGURATION ID 2
WHITE STICKER TITLED “ORIGINAL FACTORY UNIT CONFIGURATION” LOCATED ON THE
RIGHT SIDE OF THE CONTROL BOX NEAR THE M3 CONTROLLER.
CATALOG NUMBER LOCATED ON UNIT NAMEPLATE
SERIAL NUMBER LOCATED ON UNIT NAMEPLATE
RTU DESCRIPTION = UP TO 18 ALPHA/NUMERIC CHARACTERS
DEHUMIDIFIER
SENSOR TYPE
= NONE OR REHEAT DI4
= LOCAL SENSOR OR
NETWORK SENSOR
DEHUMIDIFIER DEHUMID SETPOINT = X.XX %
DEHUMIDIFIER DEHUMID DEADBAND = X.X %
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS
NETWORK
INTEGRATION
NETWORK =
L-CONNECTION
LCONN ADDRESS = X
CONTROL MODE =
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPEATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 *
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
* OCC (OCCUPIED) BLOWER MODE DESCRIPTION:
AUTO CYCLE: BLOWER CYCLES WITH DEMAND
ON-CONTINUOUS 1: BLOWER IS ON WITH EITHER THE OCCUPANCY SENSOR OR OCCU
PANCY SCHEDULER INDICATES OCCUPIED.
ON-CONTINUOUS 2: BLOWER IS ON ONLY WITH BOTH THE OCCUPANCY SENSOR AND
OCCUPANCY SCHEDULER, BOTH INDICATES OCCUPIED.
ON-CONTINUOUS 3: BLOWER IS ON ONLY WHEN BOTH THE OCCUPANCY SENSOR AND
OCCUPANCY SCHEDULER INDICATES OCCUPIED. IN ADDITION, BLOWER WILL BE ON A
MINIMUM OF 25% OF THE TIME WHEN OCCUPANCY SCHEDULER INDICATES OCCUPIED
BY THE OCCUPANCY SENSOR INDICATES NOT OCCUPIED. THE 25% MINIMUM IS
ACHIEVED BY TURNING BLOWER ON FOR 30 MINUTES AND OFF FOR 90 MINUTES.
NETWORK = BACNET
BACNET MAC ADDRESS = X
BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K
CONTROL MODE =
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 (SEE DESCRIPTION ABOVE)
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F