Table 58. Menu Interface (Level 1 - SETUP)
Level 2 Level 6Level 5Level 4Level 3
NETWORK = LONTALK
CONTROL MODE =
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR ON-
CONTINUOUS 1, 2 OR 3 (SEE DESCRIPTION ABOVE)
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR BACKUP
OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK = RTU
STANDALONE
BACKUP MODE =
NONE OR RETURN AIR
BACKUP
SETPOINTS HEAT = XX.X F
SETPOINTS COOL = XX.X F
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS.
TEST &
BALANCE
BLOWER
BLOWER CALIBRATION HIGH SPEED = CALIBRATION DONE OR TURN BLOWER ON
BLOWER HEAT = XXXX CFM
BLOWER COOLING HIGH = XXXX CFM
BLOWER COOLING LOW = XXXX CFM
BLOWER VENTILATION = XXXX CFM
ON (TARGET XXXX CFM) ADJUST BLOWER RPM = XXXX RPM
DAMPER
ECONOMIZER TEMP ECON TYPE = TEMPER
ATURE OFFSET OR TEMPERATURE SETPT
NOTE: THIS OPTION IS DEPENDANT ON
CONFIGURATION ID 1 SETUP.
ECONOMIZER OAT SETPOINT = XX.X F.
ECONOMIZER ENTHALPY SETPOINT = XX
MA
NOTE: THESE OPTIONS ARE DEPENDANT ON
CONFIGURATION ID 1 SETUP.
ECONOMIZER ENTHALPY OFFSET = XX MA
FREE COOLING SUPPLY AIR SETPOINT = XX.X F
DAMPER OUTDOOR AIRFLOW = XXX CFM
ADVANCE AIRFLOW ALARMS = ENABLED OR
DISABLED (ONLY VISIBLE IF CONFIGURATION
ID 1, POSITION 2 IS SET CORRECTLY).
ADV AIRFLOW ALARMS LO SPLY AIRFLOW
ALM = XX%
ADV AIRFLOW ALARMS LO OD AIRFLOW ALM
= XX%
ADV AIRFLOW ALARMS HI OD AIFLOW ALM =
XX%
ADV AIRFLOW ALARMS ALM TRIGGER PERI
OD = XXXX SEC
MIN DAMPER POSITION BLOWER ON HIGH = X.X %
MIN DAMPER POSITION BLOWER ON LOW = X.X %
DEMAND CONTROL VENT > DAMPER START OPEN = XXX PPM
DEMAND CONTROL VENT > DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT > DAMPER MAX OA CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1, POSITION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT > DAMPER MAX OPENING = XXX.X %.
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
FRESH AIR HEATING
ENABLE FAH = NO OR
YES
FRESH AIR HEATING FAH SETPOINT = XX F
FRESH AIR COOLING
ENABLE FAC = YES OR
NO
FRESH AIR COOLING AFC SETPOINT = XX F
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS.