Table 63. M3 Control Parameters
Control Parameter
DescriptionUnits
Control Value
No DescriptionUnitsMax.DefaultMin.
Parameter Short
Description
Screen Name
189 SRV OUTPT SP TEMP
Service Output Set Point
Temperature
-31.0 51.0 132.0 °F
Service Output Set Point Tem
perature
190 SRV OUTPT DB C02
Service Output
Deadband for Carbon
Dioxide
16 102 2000 ppm
A55 service relay output dead-
band or delay.
191 SRV OUTPT DB RH
Service Output
Deadband for Relative
Humidity
2.0 13.0 100.0 %
Service Output Deadband for
Relative Humidity
192 SRV OUTPT DB TEMP
Service Output
Deadband for
Temperature
1.0 8.0 162.0 °F
Service Output Deadband for
Temperature
193 SRV OUTPT DELAY Service Output Delay 64 416 8160 Seconds Service Output Delay
194
LOAD SHED NUM
COMP
Number of compressors
to shed during load
shedding
0 0 4 Option
Number of compressors to be
turned off when load shedding
is active.
Applicable to Energence Stan
dard Efficiency 3- to 6-ton units
only. 2-stage compressor, a val
ue of one shuts off 2nd stage
only and a value of 2 turns com
pressor completely off.
196 MAC ADDRESS MAC Address 0 128 128 Address
BACnet MAC Address. A value
of 0-128 sets the BACnet MAC
address to that value.
197 BAUD RATE Baud Rate
9.6K
19.2K
38.4K
76.8K
Option Baud rate setting.
System 3 Parameters
201
DACC OAT RS ADJ
BND
Discharge Air Control
Cooling Outdoor Air
Temperature Adjustment
Band
0.0 0.0 30.0 °F
Discharge Air Control Cool
ing outdoor temperature am
bient cooling adjustment re
set band.
Also used to reset free cool
ing set point (parameter 159).
202 DACC OAT RS ADJ SP
Discharge Air Control
Cooling Outdoor Air
Temperature Cooling
Reset Set Point
40.0 80.0 100.0 °F
Discharge Air Control Cool
ing outdoor air temperature
cooling reset set point.
Also used to reset free cool
ing set point (parameter 159).
203
DACC OAT RS PRP
BND
Discharge Air Control
Cooling Outdoor Ambient
Air Temperature Cooling
Proportional Band
1.0 20.0 60.0 °F
Discharge Air Control Cool
ing outdoor ambient temper
ature cooling proportional
band.
Also used to reset free cool
ing set point (parameter 159).
204 DACC RAT RS ADJ BND
Discharge Air Control
Cooling Return Air Reset
Adjustment Band
0.0 0.0 30.0 °F
Discharge Air Control Cool
ing return air reset adjust
ment band. 0 disables return
air cooling reset.
Also used to reset free cool
ing set point (parameter 159).
205 DACC RAT RS ADJ SP
Discharge Air Control
Return Air Reset
Adjustment Set Point
50.0 70.0 80.0 °F
Discharge Air Control Cool
ing return air reset set point.
Also used to reset free cool
ing set point (parameter 159).