Item Settable range Default Remarks
Link with
Fresh Air IDU
ON, OFF OFF
After setting the linkage function, the
fresh air IDU will automatically turn on
or turn off along with the on and off of
general IDU, meanwhile, user can
manually turn on or turn off the unit.
Only applicable to fresh air IDU.
PM2.5 filter* ON, OFF OFF
After it is successfully set, adjust the
revolving speed to ensure the air
volume is close to or the same as the
previous air volume.
Only applicable to the unit with PM2.5
In ℉
ON, OFF ON
When it is set as “ON”, the temperature
unit becomes Fahrenheit, otherwise the
Clear Filter
Cleaning Time
Clear Filter
Cleaning Time?
--
Reset WiFi Reset WiFi?
Only applicable to the unit connected to
“G-cloud control”.
1~9
5 --
Number of
IDUs
0: disable this
function
1-16: quantity of
1
Set corresponding value according to
the connected quantity of IDU.
Air-return
Angle 2
Angle 1
Only applicable to the model with
air-return plate.
Cooling temp of
Auto Mode
17℃~30℃ 25℃
Cooling temperature of Auto mode –
heating temperature of Auto mode≥1℃.
Heating temp of
Auto Mode
16℃~29℃ 20℃