CDU Operating & Maintenance Guide Page 17
Neptune DWC RM100 in-rack Coolant Distribution Unit
Configuration – Temperature Control
Set required Secondary temperature setpoint
Select from Fixed Setpoint or Fixed Setpoint
with Dewpoint Override
Minimum offset of setpoint from dewpoint
temp.
Minimum offset of setpoint from ambient temp.
Low temp alarm offset below setpoint
High temp alarm offset above setpoint
Sec. Temp Reset Hysteresis
Low/High temp. alarm reset point
Sec. High Temp Setpoint DW
High temp alarm offset above setpoint when
dewpoint or ambient tracking
Scan period for control valve positioning
Control valve demand to feedback error for
alarm
Scan period for control valve position
monitoring
Control valve motor run time for control loop
Max Cooling Mode Temp
Setpoint
The temperature setpoint used when operating
in Max Cooling Mode
Time delay prior to low flow alarm
High temp alarm threshold
Pri. Temp Reset Hysteresis
Low/High alarm reset from threshold
Sec. Filter Dirty Setpoint
Differential pressure alarm threshold for filter
dirty
Sec. Filter Dirty Hysteresis
Alarm reset from threshold
Sec. Filter Dirty Delay Period
Time delay prior to alarm
Configuration – Leak Detection
Leak Detection Operation -
Internal
Alarm only, or shutdown & alarm
Set sensitivity of leak tape
Time delay prior to alarm
Leak Detection Operation –
Primary External
Alarm only, or shutdown & alarm
Leak Detection Operation –
Secondary External
Alarm only, or shutdown & alarm
Secondary T2 Temperature
Differential
Alarm threshold T2a/b/c temperature differential
Time delay before T2a/b/c differential alarm
Set measurement range. 0 = 0 to 30bar, 1 = 0
to 15bar, 2 = -1 to 8 bar.