EasyManua.ls Logo

Lenovo Neptune DWC RM100 - Fig.19 - Water Level Management Flow Chart (When Running)

Lenovo Neptune DWC RM100
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CDU Operating & Maintenance Guide Page 25
Neptune DWC RM100 in-rack Coolant Distribution Unit
Pump flow/pressure performance (pump speed) can be controlled through either a flow or
differential pressure control loop depending on Configuration (see Configuration - Pump Control).
Flow Control
Monitors the Secondary flow with a calorimetric flow meter and on start-up, the control loop will
increase the pump speed in stages until the flow matches the demand setpoint.
DP Control
Monitors the Secondary differential pressure with sensors on the supply & return connections of the
CDU and on start-up, the control loop will increase the pump speed in stages until the DP matches the
DP setpoint.
The pump control loop has a default scan time of 10 seconds to avoid control oscillation.
- If Pump 1 fails to reach 90% (default) of the flow/DP demand in a default time period of 100secs,
then it is assumed there is a pump flow/pressure fault. The pump will ramp down to a stop and
Pump 2 will be initialised. At the same time, an ‘A17 Pump 1 Fault alarm will be generated.
- If Pump 2 also fails to reach 90% of the set DP/flow demand within the time limit, an ‘A18
Pump 2 Fault’ alarm will be generated.
- The unit will then continue to operate with Pump 2 until faults are investigated and alarms
manually cleared.
- The above assumes Pump 1 is the initial operating pump, the reverse would apply if Pump 2
was the operating pump.
During normal healthy running for run/standby pump operation, the pumps will operate on a duty
sharing cycle, i.e. every 7 days (default) the operational pump will ramp down to a stop and the standby
pump will then start and continue operating for the next 7 days etc. Changeover default time is set at
10:00am on a Monday morning (default) and the complete changeover sequence takes approx. 0.25
seconds (default).
NOTICE! Each time the unit is stopped and re-started, it will select the initial
operating pump that has the lowest accrued run time hours.
RM100 water level
management
RM100 stops
Water level
sensor open
circuit >1 sec?
Y
N
N
Is Flow/DP
>50% of SP
Y
RM100 continues
to run
A34 Level
Sensor No Water
A16 Insufficient
Water
Unit running, with make-up
fill bag connected
Fig.19 Water Level Management Flow Chart (when running)

Table of Contents

Related product manuals