CDU Operating & Maintenance Guide Page 19
Neptune DWC RM100 in-rack Coolant Distribution Unit
Service - Fill Pump Request
This fill function is used at commissioning
only and will allow the fill pump to run
without any time limit. Fill pump will still
switch Off automatically when unit reaches
required static pressure
Used to force a pump changeover at an
unscheduled time.
Service - Suppress Alarms
Resets the alarm delay timer (normally only
activated during start-up) to stop nuisance
alarms breaking through during manual
operation
Set pump drive control speed
Set pump drive control speed
Set control valve position
Switch alarm output on or off
‘Overrides’ allows the user to manually control some functions of the unit for a limited time period while running in automatic
mode, for the purposes of troubleshooting etc. (see Installation & Commissioning manual for more information).
Service – Reset Run Hours
Resets the pump and valve run hours to zero.
Service – Full Manual Control
Set unit to full manual control
Set pump drive control speed
Set pump drive control speed
Set control valve position
Switch alarm output on or off
Switch pump cooling fan on or off
Service – Max Cooling Mode
The function of this mode is to instantly
provide the maximum possible cooling in an
emergency situation