What to do if Lenze Control Unit does not execute write job?
- RRichard MortonAug 17, 2025
If the Lenze Control Unit doesn't execute a write job, it might be due to an incorrect operating mode (C0001) for writing to codes C0046 and C0135, or the code might be read-only. Set parameter 3 for operating mode C0001. If the controller sends a positive acknowledgement, activate controller inhibit and change over the parameter set. This activates the parameter change. Also, ensure the controller isn't using a different parameter set by activating controller inhibit and changing over the parameter set.