Appendix
8-3
L _^ONMObk
8.2 Code table
How to read the code table:
Code Code number of the parameter Leading zeros are not required.
Codes marked with
*
are only available in parameter set 1.
Name Name of the parameter
The text in parenthesis informs whether the codes are available in the fieldbus module or the
controller:
(P2102): Paramet ers in the fieldbus module 2102IB
(P820X/P821X/8200 vector/822X):
Parameters in controllers 820X, 821X and 822X.
The parameters can also be set via the 8201BB keypad.
(P93XX):Parameters in the 93XX controller.
The parameters can also be set via the 9371BB keypad.
Parameters Contents and meaning of the parameter
values
ParametersprintedinboldaresetbyLenze.
Code Name Note
C0001 Operating mode for
82XX 8200 vector
C
0
0
0
1
O
p
e
r
a
t
i
n
g
m
o
d
e
f
o
r
82XX
8200 vector
(P82XX)
0 Control (C0135): Terminal
Setpoint (C0046): Terminal
(Lenze setting: 0)
1 Control (C0135): Terminal
Setpoint (C0046): Keypad:
2 Control (C0135): Terminal
Setpoint (C0046): Terminal
3 Control (C0135): LECOM
Setpoint (C0046): LECOM
The operating mode defines the source which
writes on a parameter.
The keypad and LECOM always have the right to
parameterize.
LECOM format: VD
see Operating Instructions ’Vector
C0009
*
LECOM controller
address
(P82XX)
(P93XX)
1 1to99
Controller address for unique address in a LECOM-A/B/LI network.
Do not set the values 00, 10, ..., 90, since they a re reserved fo r group addressing.
LECOM format: VD
C0040
*
Controller inhibit
(P2102)
0 Controller inhibited
1 Controller enabled
Parameter C0040 is independent of operating mode C0001.
The controller can also be enable with control word C0135.
LECOM format: VD
C0043
*
TRIP reset for:
821X
8200 vector
822X
93XX
(P2102)
0 No a ctual fault, fault reset by overwriting with
value 0
1Actualfault
Parameter C0043 is independent of operating mo de C0001. A TRIP can also be reset using the control word C0135. (TRIP
reset for 820X, see chapter 6.4)
LECOM format: VD
C0046
*
Frequency setpoint for:
820X
(P2102)
0 t o 480 Hz
LECOM format: VD
Frequency setpoint for:
821X
8200 vector
822X
(P821X/P8200 vector/P822X)
Speed setpoint for 93XX
(C0046 can only be
read.)
0 t o 480 Hz
The value can be changed t hrough the display factor C500/C501 (see Code ta ble included in the Operating Instructions 820X,
821X and 822X).
For 93XX, the f re e control code C0141 is used as speed setpoint in % o f n
max
if the basic configuration is C0005=1001.
LECOM format: VD