Technical data
3-1
BA2131EN
3 Technical data
3.1 Features of the 2131 fieldbus module
The 2131 fieldbus module has the following features:
l
Attachable additional module for Lenze controller series 820X, 821X, 8200 vector, 822X and
93XX
l
Slave interface module for the communication system PROFIBUS with the communication
profile PROFIBUS-DP (DIN19245 part 1 and part 3)
l
Automatic baud rate detection
l
Baud rate between 9.6 kbaud and 12 Mbaud
l
Optionally 4 or 6 byte proces data
l
Optional parameter-setting channel
l
Access to all Lenze parameters
l
Application profile: DRIVECOM Profil 20
3.2 General data / application conditions
Field Values
Order designation 33.2131IB
Communcation medium RS485
Network topology Line
Max. cable length 1200 m (depending on the desired baud rate and the cable type used)
PROFIBUS participants Slave
Communication profile PROFIBUS-DP (DIN 19245 part 1 and part 3)
Drive profile DRIVECOM profile 20
Baud rate 9.6 kbit/s to 12000 kbit/s
Ambient temperature during operation: 0 to 50
C
Transport: -25 to 70
C
Storage: -25 to 55
C
Permissible humidity Class 3K3 to EN 50178 (without condensation, average relative humidity 85%)
24-V-DC-
Voltage supply
l
820X / 8200 vector (observe chapter 4.3.1): only external supply
l
821X / 822X / 8200 vector (observe chapter 4.3.1) / 93XX: internal or external supply