DeviceNet
10 Installation
10-7
L BA2175 EN 2.0
10.5 Features of the “ thin” cable (according to DeviceNet Specification)
General f eatures
Two shielded pairs Common axis with drain wire in center.
Total shielding 65% coverage
36 AWG or 0.12mm Cu braid (individually tinned)
Drain wire #22 copper min.; 19 AWG min. (individually tinned)
Outside diameter 6.096 mm (min) to 7.112 mm (max.) roundness - radius delta to be within 20% of 0.5
O.D.
Jacket marking Vendor name & part # and additional markings
DCR (braid+tape+drain) 10.5 Ohm/1000 m (nom. @ 20ºC)
General f eatures Specification
Certifications (U.S. and Canada) NEC (UL) type CL2(min.)
Bend readius installation / fixed 20 x diameter / 7 x diameter
Oprating ambient temperature -20 to +70ºC @ 1,5 Ampere; de-rate current linearly to zero @ 80ºC
Storage t emperature -40 to +85ºC
Pull tension 289.23 N. max.
Features of the
Insulation diameter 1.96 mm (nominal)
data cable
Conductor pair size #24 copper (minimum); 19 AWG min (individually tinned)
Colours libht blue blue, white
Pair twist / m approx. 16
Tape shield over pair 1 mil / 1 mil, Al / Mylar. Al side out
w/shorting fold (pull-on applied)
Impedance 120 Ohm + /- 10% (at 1 MHz)
Propagation delay 4.46 ns/m (maximum)
Capacitance between conductors 39.37 pF / m at 1 kHz (nominal)
Capacitance between a conductor and the
conductor connected to shield.
78.74 pF / m at 1 kHz (nominal)
Capacitive unbalance 3.94 pF/1000 m a t 1 kHz (maximum)
DCR - @ 20ºC 91.86 Ohm/1000 m (maximum)
Attenuation: 0.95 dB/100 m @ 125 k H z (maximum)
1.64 dB/100 m @ 500 k Hz (maximum)
2.30 dB/100 m @1.00MHz (maximum)
Features of the
Conductor pair size #22 copper (Minimum); 19 AWG Minimum (individually tinned)
voltage cable
Insulation diameter 1.4 mm (nominal)
Colours Red
Black
Pair twist/m approx. 16
Tape shield over pair 1 mil / 1 mil, Al / Mylar. Al side out
w/shorting fold (pull-on applied)
DCR - @ 20ºC 57.41 Ohm/1000 m (maximum)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com