CANopen
6 Parameter setting
6-56
L
BA2175 EN 2.0
See L-C1876 / L-C2376.
6.5.2.20 L-C1878/L-C2378: CAN-OUT3 masks
This mask is used to skip one or several bits of the CAN-OUT3 output PDO.
Possible settings
Code
Subcode
Inde
Lenze Selection Data type
L-C1878
/1 CAN-OUT3.W1
/2 CAN-OUT3.W2
58A9
h
= 22697
d
65535 0 [1] 65535 FIX32
L-C2378
/3 CAN-OUT3.W3
/4 CAN-OUT3.W4
56B5
h
= 22197
d
See L-C1876 / L-C2376.
6.5.2.21 L-C1882/L-C2382: Monitoring response
Possible settings
Code
Subcode
Inde
Lenze Selection Data type
L-C1882
/1 CAN-IN1 response
/2 CAN-IN2 response
/3 CAN-IN3 response
58A5
h
= 22693
d
0 0[1]2
0: No response
FIX32
L-C2382
/4 BUS-OFF response
/5 Life guarding event
response
56B1
h
= 22193
d
1: Controller inhibit
2: Quick stop
FIX32
Setting of the response after the monitoring time (see L-C1857/L-C2357) has been exceeded.
Note!
A monitoring response change becomes effective immediately.
CANopen relation
The CANopen indexes 100C
h
“guard time” and 100D
h
“life time factor” canbeusedtosetatime
for the node guarding p. The node guarding protocol has been developed for monitoring the
master/slave connection. A time in milliseconds can be entered in CANopen index 100C
h
“guard
time”. Index 100D
h
“life time factor” saves a factor. The monitoring time (time in which the master
sends a certain telegram to the slave/2175 IB)results from multiplying the two indexes. If one of the
indexes is set to zero, the monitoring time is zero too and thus deactivated. The slave sends a
telegram with its current NMT status to the master. The status can be preoperational, operational
or stopped.
If the monitoring time is exceeded, theslave respondswith alife guardingevent and the masterwith
a node guarding event.
The node guarding protocol must be programmed and started in the master. The 2175IB module
supports the node guarding protocol, a response can only be entered under this code.
6.5.2.22 L-C2120: AIF control byte
Possible settings
Code Subcode Index Lenze Selection Data type
L-C2120 - 22455
d
= 57B7
h
0 0 = No command
1 = Code L-23XX update and CAN
re-initialisation
≡ Reset node
2 = Code L-C23XX update
10 = Reading o f L-C2356/1...4
11 = Reading of L - C2357
12 = Reading of L - C2375
13 = Reading of L-C2376 ... L - C2378
14 = Reading of L - C2382
15 = Not assigned
FIX32
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com