CANopen
6 Parameter setting
6-17
L BA2175 EN 2.0
Process data telegram from controller
User data length: 8 byte
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Identifier
Status word
L-C0150
Low byte
Status word
L-C0150
High byte
Actual value
L-C0050
Low byte
Actual value
L-C0050
High byte
xx xx xx xx
Byte 1 Bits 0 to 7 of the status word under L-C0150 are entered here
Byte 2
Bits 8 to 15 of the status word under L-C0150 are entered here (seen chapter 6.3.4.2).
The bit description can be obtained from the Code T able.
More information
Byte 3
Actual frequency value with signed normalisation (L-C0050)
about the process
Byte 4
24000 = 480 Hz is provided here.
a
a
Byte 5
Byte 6
Byte 7
No evaluation of these data, anything possible
Byte 8
Status word: see chapter 6.3.4.2.
16 bit
16 bit
.B15
.B12
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B13
.B14
.B5
.B6
.B7
IMP
fd=fdset/RFG
Qmin
Imax
-/fd=fdset
PAR
fd>0
Ctrl. inhibit
Ugmax
CW/CCW
RDY
T
ü
AIF
C0050
Status
word
Controller
status
+/-24.000 = +/- 480Hz
2141LON012
Fig. 6-4 Read access to status word and actual frequency value in 82XX (fixed, see (^ 6-21) )