Automation
Fieldbus function modules
Lenze
3-23
8200 motec/starttec en 12/03
3
PROFIBUS-DP
Communication medium RS485
Communication profile PROFIBUS-DP (DIN 19245 Part 1 and Part 3)
Drive profile DRIVECOM profile "Drive technology 20"
1)
or Lenze device control
Baud rate [kbps] 9.6 ... 12000 (automatic detection)
PROFIBUS-DP participant Slave
Network topology Without repeaters: Line
With repeaters: Line or tree
Process data words (PZD) (16 bits) 1 word... 10 words
DP user data length Parameter channel (4 words) + process data words
No. of stations Standard: 32 (= 1 bus segment) including control system
With repeaters: 128 including control system and repeaters
Max. cable length per bus segment 1200 m (depending on baud rate and cable type used)
Communication time • Sum of scan time and processing time in the
fieldbus participants. The times are independent of one another.
• Processing time in the controller:
– Parameter data and process data are independent of each other
– Parameter data: Approx. 30 ms + 20 ms tolerance
– Process data: Approx. 3 ms + 2 ms tolerance
Electrical connection Screw terminals
Connection options Rigid: 1.5 mm
2
(AWG 16)
Flexible:
1.0 mm
2
(AWG 18) without wire crimp cap
0.5 mm
2
(AWG 20) with wire crimp cap without plastic crimp cap
0.5 mm
2
(AWG 20) with wire crimp cap with plastic crimp cap
DC voltage supply Internal
for the function module • External
– Only required for bus devices which are to be disconnected from the
mains, but communication with the master is to be maintained
– Required for bus devices with activated bus terminating resistor,
which are to be disconnected from the mains, but the bus system is
to remain active
– Power is being provided via a separate power supply
– +24 VDC ± 10%, max. 80 mA per function module
Isolation voltage to reference earth/PE 50 V AC
Ambient temperature Operation: –20 ... +60ºC
Transport: –25 ... +70ºC
Storage: –25 ... +60ºC
Climatic conditions Class 3K3 to EN 50178
(no condensation, average relative humidity 85%)
Note:
• Two LEDs are located on the function module to indicate the communication status.
• A configuration diskette for PROFIBUS-DP containing description files for the devices (EDS files) is included in the scope
of supply.
Important:
The internal or external DC supply to the "controller inhibit" terminal (X3/28) is provided
independently of the internal or external DC supply to the function module.
Tip:
The external DC supply to the function module is provided via terminals X3/59 and X3/7.
The connection diagrams above indicate the internal DC supply to the function module as an alternative option.
General data and operating conditions
1)
Not supported when using the fieldbus function module with
starttec.