Safety instructions
Safety instructions for the installation according to UL/CSA
2
131
EDKVS9332X DE/EN/FR 8.0
2.4 Safety instructions for the installation according to UL/CSA
Warnings!
ƒ Motor Overload Protection
For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
ƒ Branch Circuit Protection
The integral solid state protection does not provide branch circuit
protection.
Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
ƒ Please observe the specifications for fuses and screw−tightening torques in
these instructions.
ƒ EVS9321  EVS9326:
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V maximum, when protected by fuses.
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum, when protected by CC, J, T or R
class fuses.
Maximum surrounding air temperature: 0 ... +55 °C
> +40 °C: reduce the rated output current by 2.5 %/°C
Use 75 °C copper wire only.
ƒ EVS9327  EVS9329:
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V maximum, when protected by fuses.
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum, when protected by J, T or R class
fuses.
Maximum surrounding air temperature: 0 ... +50 °C
> +40 °C: reduce the rated output current by 2.5 %/°C
Use 60/75 °C or 75 °C copper wire only.
ƒ EVS9330  EVS9332:
Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 480 V maximum, when protected by fuses.
Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum, when protected by J, T or R class
fuses.
Maximum surrounding air temperature: 0 ... +50 °C
> +40 °C: reduce the rated output current by 2.5 %/°C
Use 60/75 °C or 75 °C copper wire only.