5 Technical data
General data/operating conditions
EDK82ZAFVC010 DE/EN/FR 2.0
64
l
H1daten−abmess
5 Technical data
General data/operating conditions
Field Values
Order designation E82ZAFVC010 PT version
Communication medium DIN ISO 11898
Communication profile DeviceNet
Network topology Line terminated at both ends (R = 120 Ohm)
Max. number of participants 63
DeviceNet participant Slave
Baud rate [kbit/s] 125, 250, 500
Max. possible bus cable length depending on the cable used, see ^ 55
External voltage supply see ^ 52
Type of protection IP20
Ambient temperature
Operation: −20 °C ... +60 °C
Transport: −25 °C ... +70 °C
Storage: −25 °C ... +60 °C
Climatic conditions Class 3K3 according to EN 50178 (without condensation,
average relative humidity 85 %)
Degree of pollution EN 50178, pollution degree 2
X3.1/
V+
External DC voltage supply for the function module:
+24 V DC ±10 %, max. 80 mA
The current flowing via terminal V+ when looping through the supply voltage to other
bus devices must not exceed 3 A.
X3.2/
7 Reference potential 1
39 Reference potential 2 of controller inhibit (CINH) at X3.2/28
28 Controller inhibit
l Start = HIGH (+12 V ... +30 V)
l Stop = LOW (0 V ... +3 V)
Input resistance: 3.3 kW
20 + 20 V internally for CINH, reference potential 1, load capacity: I
max
= 30 mA