Code table
10
Function library
10.20
L
10.20-44
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0501* Calibration of
denominator
process variable
10 1 {1} 25000 • The codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039, C0044,
C0046, C0049, C0050, C0051, C0138,
C0139, C0140, C0181, C0239, C0625,
C0626, C0627 can be calibrated in a
way that the keypad indicates a process
variable.
• If C0500/C0501 remain unchanged, the
unit ”Hz” will no longer be displayed.
^ 10.16-1
C0500*
(A)
Calibration of
numerator variable
2000 1 {1} 25000
• The codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051, C0138,
^ 10.16-1
C0501*
(A)
Calibration of
denominator
process variable
10 1 {1} 25000
C0139, C0140, C0181 can be calibrate d
in a way that the keypad indicates a
process variable with t he unit selected
C0502*
(A)
Process variable
unit
0 0: —
1: ms
2: s
4: A
5: V
6: rpm
9: °C
10: Hz
11: kVA
12: Nm
13: %
14: kW
15: N
16: mV
17: m
Ω
18: Ω
19: hex
34: m
35: h
42: mH
un
er
.
• Frequency-relat e d codes (C0010,
C0011, C0017, C0019, C0050, C0239,
C0625, C0626, C0627) are always
indicatedin”Hz”.
C0517*
v
User menu
• After mains switching or when using the
function
g the code from C0517/1
^ 10.18-1
1 Memory 1 50 C0050 Output frequenc y (MCTRL1-NOUT)
will be displayed.
2 Memory 2 34 C0034 Analog setpoint selection range
•
n
enze se
ng,
e user menu con
a
ns
h
m
im
r
n
f
r
in
3 Memory 3 7 C0007 Fixed configuration - digital input signals
the control mode ”V/f characteristic
4 Memory 4 10 C0010 Minimum output frequency
control with linear characteristic”
5 Memory 5 11 C0011 Maximum output frequency
• When the password protection is
6 Memory 6 12 C0012 Acceleration time main setpoint
ac
va
e
,on
y
eco
es en
ere
un
er
C0517 are freel
accessible.
7 Memory 7 13 C0013 Deceleration time main setpoint
.
• Enter the required code numbers in the
8 Memory 8 15 C0015 V/f rated frequency
subcodes.
9 Memory 9 16 C0016 U
min
boost
Codes, which are on ly active when
10 Memory 10 2 C0002 Parameter set transf er
e
ng use
oge
er w
an
lication-I
O
cannot be entered!
C0518
Service codes Modifications only by Lenze Service!
C0519
C0520
C0597* Configuration of 0
0 not active
v
motor phase failure
1 TRIP fault message Keypad: LP1, bus: 32
detection
2 Warning Keypad: LP1, bus: 182
C0599*
v
Current limit value
for motor phase
failure detection
5 1 {1 %} 50 • Threshold for C0597
• Reference: Rated controller current
C0608* Monitoring of 0
0 not active
Function o nly active with 8200 mot e c 3 ...
external fan
1 TRIP fault message
Keypad:
Err95
Bus: 95
7.5 kW
With all other controller it is absolutely
necessa ry to set C0608 = 0
2 Warning
C0625* Skip frequency 1 0.00 0.00 {0.02 Hz} 650.00
^ 10.4-6
C0626* Skip frequency 2 0.00 0.00 {0.02 Hz} 650.00
C0627* Skip frequency 3 0.00 0.00 {0.02 Hz} 650.00
C0628* Bandwidth of skip
frequencies
0.00 0.00 {0.01 %} 100.00 Applies to C0625, C0626, C0627
C0988* DC-bus voltage
threshold for
DC-bus voltage
control
0 0
Parameter set
changeover via
DC-bus voltage
deactivated
{1 %} 200 • Changeover always between PAR1 nd
PAR2
• Parameter set changeover is not
possible via terminal, bus or PC if C988
>0!
^ 10.5-4
^ 10.7-8