EasyManua.ls Logo

Lenze E84DGFCp Series - Bus Cable Specification

Lenze E84DGFCp Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDS84DMOTPBUS EN 3.0 - 11/2011 L 25
Communication manual 8400 motec PROFIBUS
Installation
Electrical installation
5.2.3 Bus cable specification
Bus cable length
The bus cable length depends on the baud rate used:
Tip!
For high baud rates, we recommend taking the use of optical fibres into
consideration.
Advantages of optical fibres:
External electromagnetic interferences have no effect on the transmission
path.
Bus lengths of several kilometres are also possible with higher baud rates.
The bus length is ...
independent of the baud rate;
dependent on the optical fibre used.
Note!
Only use cables that correspond to the given specifications of the PROFIBUS user
organisation.
Area Values
Cable resistance 135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length 30 nF/km
Loop resistance < 110 Ω/km
Core diameter > 0.64 mm
Core cross-section > 0.34 mm
2
Cores Twisted in pairs, insulated and shielded
Baud rate Length
9.6 ... 93.75 kbps 1200 m
187.5 kbps 1000 m
500 kbps 400 m
1500 kbps 200 m
3000 ... 12000 kbps 100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations
should only be selected as high as required for the application.

Table of Contents

Related product manuals