Communication manual 8400 motec PROFIBUS
Process data transfer
Digital and analog input information
40 L EDS84DMOTPBUS EN 3.0 - 11/2011
8.3 Digital and analog input information
In addition to the process data, digital and analog input information can also be queried.
The signals are set permanently to 2 additional data words which must be parameterised
correspondingly in the HW manager.
Word Bit Function Values / states
1 0 Analog input value (0 ... 10 V) 10 V = 1000
dec
(1111101000
bin
)
...
9
10 Digital input 3 0: Closed / not active
1: Open / active
11 Digital input 4 0: Closed / not active
1: Open / active
12 Digital input 5 0: Closed / not active
1: Open / active
13 Reserved
14 I/O status 0: I/O data are invalid.
1: I/O data are valid.
15 Drive status 0: Controller is 'offline'.
1: Controller ist 'online'.
2 0 RFR (controller enable) 0: Controller is enabled.
1: Controller is not enabled (inhibited).
1 Digital input 1 0: Closed / not active
1: Open / active
2 Digital input 2 0: Closed / not active
1: Open / active
3 Digital input 3 0: Closed / not active
1: Open / active
4 Digital input 4 0: Closed / not active
1: Open / active
5 Digital input 5 0: Closed / not active
1: Open / active
6 Reserved
...
13
14 I/O status 0: I/O data are invalid.
1: I/O data are valid.
15 Drive status 0: Controller is 'offline'.
1: Controller ist 'online'.