Configuration
Configuring system bus (CAN)
Node guarding
8
103
EDBCSXE040 EN 6.0
Parameter
C0383
Designation
CAN Node Guarding: "Node Life Time Factor"
Data type: INTEGER_32
Index: 24192
dec
= 5E80
hex
Factor for monitoring time "Node Life Time"
l Node Life Time = C0383 x C0382
l Only relevant if C0352 = 2.
102
Setting range (min. value | unit | max. value) Lenze setting
0 255 0
Parameter
C0384
Designation
Response − CAN node guarding
Data type: INTEGER_32
Index: 24191
dec
= 5E7F
hex
Response to a "Life Guarding Event"if no node guarding telegram has been received during "Node Life Time"
(C0382 x C0383).
l When C0382 = 0 or C0383 = 0, the monitoring function is not active (no node guarding fault message is
enabled).
l Only relevant if C0352 = 2.
102
Selection list (Lenze setting printed in bold) Information
0 TRIP
1 Message
2 Warning
3 Off