Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
5
35
EDBCSXE040 EN 6.0
Shielding
ƒ Connect the motor cable shield to the axis module
with the ECSZS000X0B shield mounting kit.
to the mounting plate below the axis module with a large surface.
Recommendation: For the shield connection, use ground clamps on bare metal
mounting surfaces.
ƒ If contactors, motor−protecting switches or terminals are located in the motor cable:
Connect the shields of the connected cables and connect the shields to the
mounting plate, too, with a surface as large as possible.
ƒ Connect the shield in the motor terminal box or on the motor housing to PE:
Metal glands at the motor terminal box ensure a large−surface connection of the
shield and the motor housing.
ƒ Shield the control cables:
Connect both shield ends of the digital control cables.
Connect one shield end of the analog control cables.
Always connect the shields to the shield connection at the axis module over the
shortest possible distance.
ƒ Using the axis modules in residential areas:
Additionally dampen the shield in order to limit the interfering radiation: ³10 dB .
This can be implemented by using standard, closed, metallic, and earthed control
cabinets or boxes.
Earthing
ƒ Earth all metallically conductive components (e. g. power supply module, capacitor
module, axis module, RFI filter, motor filter, mains choke) using suitable cables
connected to a central point (PE bar).
ƒ Maintain the minimum cross−sections prescribed in the safety regulations:
For the EMC, not the cable cross−section is important, but the cable surface and the
contact surface which should be as large as possible.