Connecon via terminal box
Observe the notes on wiring, data on the nameplate, and the connecon diagram in the
terminal box.
The connecon must ensure a connuous and safe electrical supply:
No protruding wire ends
Use assigned cable end ngs
Ensure good electrical conducvity of the contact (remove paint residues) if an addional
PE connecon is used
Establish a safe protecve earth connecon
Aer the connecon is completed, make sure that all connecons on the terminal board
are rmly ghtened
The terminal box has to be free of foreign bodies, dirt, and humidity
All unused cable entries and the terminal box itself must be sealed so that they are dust-
ght and waterproof
The smallest air gaps between uncoated, live parts and against earth must not fall below the
following values:
Minimum requirements for basic insulaon
according to IEC/EN 60664-1 (CE)
Higher requirements for UL design Motor diameter
3.87 mm 6.4 mm <178 mm
9.5 mm > 178 mm
Posion of the connecons
1
2
Note Meaning Note
1 Power connecon
Brake connecon
PE connecon
Feedback connecon
Connecon of temperature monitoring
2 Blower connecon If required, the terminal box cover can be rotated step by step by
90 ° aer loosening the screws on the terminal box.
Electrical installaon
Motor connecon
Connecon via terminal box