EasyManua.ls Logo

Lenze i500 Series

Lenze i500 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Commissioning
Operang Instrucons i510-Cabinet
Display code Name
Possiblesengs/
value ranges
Keypad code Informaon
P323.00 Motor current
0.001 ... 1.700 ... 500.000 A *
Seng of the rated motor current according to motor nameplate. With regard to rated motor current (P323.00)
P324.00 Max current 0.0 ... 200.0 ... 3000.0 % Maximum overload current of the inverter.
P400.01 Inverter enable TRUE [1] Assignment of a trigger to the “inverter enable“ funcon.
Trigger = TRUE: The inverter is enabled (unless there is another cause for inverter disable).
Trigger = FALSE: The inverter is disabled. The motor has no torque and coasts.
P400.02 Run Digital input 1 [11] Assignment of a trigger to the “Run” funcon.
Funcon1:Start/stopmotor(defaultseng)
Funcon 1 is acve if no further start commands (start forward/start reverse) have been connected to triggers, no keypad control is acve and no
network control is acve.
Trigger = TRUE: Let motor rotate forward (CW).
Trigger = FALSE: Stop motor according to stop funcon (P203.03).
Funcon2:Startclearance/stopmotor
Funcon 2 is acve if further start commands have been connected to triggers, the keypad control is acve or the network control is acve.
Trigger = TRUE: Start commands of the acve control source are enabled.
Trigger = FALSE: Stop motor.
P400.03 Quick stop Not connected [0] Assignment of a trigger to the “Acvate quick stop” funcon.
Trigger = TRUE: Acvate quick stop. Quick stop ramp P225.00.
Trigger = FALSE: Deacvate quick stop
P400.04 Error reset Digital input 2 [12] Assignment of a trigger to the “Reset error” funcon.
Trigger = FALSE > TRUE (edge): The acve error is reset (acknowledged) if the error condion is no longer acve and the error is reseable.
Trigger = FALSE: No acon.
P400.05 DC braking Not connected [0] Assignment of a trigger to the “Acvate DC braking” funcon.
Trigger = TRUE: Acvate DC braking.
Trigger = FALSE: Deacvate DC braking.
P400.06 Start forward Not connected [0] Assignment of a trigger to the “Start forward (CW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate forward.
Trigger = TRUE > FALSE (edge): No acon.Stop via P400.01 (default seng of digital input 1).
P400.07 Start reverse Not connected [0] Assignment of a trigger to the “Start reverse (CCW)” funcon.
Trigger = FALSE > TRUE (edge): Let motor rotate backward.
Trigger = TRUE > FALSE (edge): No acon.Stop via P400.01 (default seng of digital input 1).
P400.08 Run forward Not connected [0] Assignment of a trigger to the “Run forward (CW)” funcon.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.Stop via P400.01 (default seng of digital input 1).
P400.09 Run reverse Not connected [0] Assignment of a trigger to the “Run reverse (CCW)” funcon.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.Stop via P400.01 (default seng of digital input 1).
P400.13 Reverse rot. dir. Digital input 3 [13] Assignment of a trigger to the “Reverse rotang direcon” funcon.
Trigger = TRUE: The setpoint specied is inverted (i.e. the sign is inverted).
Trigger = FALSE: No acon / deacvate funcon again.
Defaultseng=boldprint|*Defaultsengisdevice-dependent

Other manuals for Lenze i500 Series

Related product manuals