23
Commissioning
Operang instrucons I510-Cabinet
7.4.4 Group7:Addionalfuncons
Display code Name Possiblesengs Keypad code Informaon
P700.01 Device commands:
Load default sengs
O/ready [0] Only status feedback
On / start [1] 1 = reset all parameters in the RAM memory of the inverter to the default seng that is stored in the inverter rmware.
All parameter changes made by the user are lost during this process!
This process may take some seconds. When the device command has been executed successfully, the value 0 is shown.
Loading parameters has a direct eect on cyclic communicaon: The data exchange for control is interrupted and a communicaon error is
generated.
P700.03 Device commands:
Save user data
O/ready [0] Only status feedback
On / start [1] Execute device commands
In progress [2] Only status feedback
Acon cancelled [3]
No access [4]
No access
(inverter disabled)
[5]