EasyManua.ls Logo

Lenze i500 Series

Lenze i500 Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Troubleshoong
Operang Instrucons i510-Cabinet
Error code Descripon Classicaon Remedy
Blockingme
[s]
Reset possible
4210 PU: Overtemperature fault Error Check mains voltage.
Ensure sucient cooling of the device (heatsink temperature displayed in P117.01).
Clean fan and venlaon slots. Replace fan if necessary.
Reduce switching frequency (P305.00).
0 Yes
4281 Heatsink fan warning Warning Clean fan and venlaon slots. If required, replace fan. The fans can be unlocked via locking hooks and can
then be removed.
0 Yes
4310 Error: Motor overtemperature Error Check drive dimensions. 5 Yes
6280 Trigger/funcons connected incorrectly Trouble Check and correct the assignment of the triggers to the funcons.
When keypad or network control is acve, the two funcons “Inverter enable” (P400.01) and “Run” (P400.02)
can also be set to “Constant TRUE [1]” to start the motor.
0 Yes
7180 Motor overcurrent Error Check motor load.
Check drive dimensions.
Adapt set warning threshold or error threshold to P353.01.
1 Yes
9080 Keypad removed Error Plug in the keypad again or acvate another control source. 0 Yes
FF06 Motor overspeed Error Adapt the maximum motor speed (P322.00) and the warning threshold or error threshold (P350.01). 1 Yes
FF37 Automac start disabled Error Deacvate start command and reset error. 0 Yes
FF85 Keypad full control acve Warning
Press the keypad key
to exit control mode.
0 Yes