Single-axis controllers
General data and operating conditions
4
45
EDS94SPP101 EN 7.1
Protective insulation
Danger!
Operation of the controller on a phase earthed mains with a rated mains
voltage of 400 V:
ƒ The protection against accidental contact is not ensured without external
measures.
ƒ If protection against accidental contact acc. to EN 61800-5-1 is required for
the control terminals of the controller and the terminals for the plugged-in
device modules,
an additional basic insulation must be available.
the components to be connected must have the second basic insulation.
Danger!
Dangerous electrical voltage
When one common voltage source is used for control voltages in separate
potential areas, the protective insulation between the separate potential areas
is deactivated.
Possible consequences:
ƒ The specified protective insulations are not complied with.
Protective measures:
ƒ Use independent voltage sources.