CONNECTING PIPES
ENGLISH
Do not insulate gas or low pressure pipe and liquid or high
pressure pipe together.
Be sure to fully insulate connecting portion.
Good example
Liquid pipe
Communication wiring cable
Communication
wiring cable
Separation
Gas pipe
Power wiring cable
Insulating material
A
B
C
D
E
Power wiring
cable
E
D
D
B
A
C
Heat insulation material
Pipe
Outer covering(Wind the connection part
and cutting part of heat insulation material
with a finishing tape.)
B
A
C
Heat insulation
material
Adhesive + Heat - resistant poly-
ethylene foam + Adhesive tape
Outer
covering
Indoor Vinyl tape
Floor
exposed
Water-proof hemp cloth +
Bronze asphalt
Outdoor
Water-proof hemp cloth +
Zinc plate + Oily paint
NOTE
!
When using polyethylene cover as cover-
ing material, asphalt roofing shall not be
required.
NOTE
!
Recommended Insulation material
Material : EPDM
Thickness : 15 mm (Gas pipe) and 19 mm (Liquid pipe) or over.
Density : less than 0.032 ±0.005(g/cm
2
)
Thermal conductivity : less than 0.03(kcal/m.hr.°C)
Cutting line of insulation must look upper direction. Thickness of insulation is 15 mm
(Gas pipe) and 19 mm (Liquid pipe) or over.
CAUTION
!
Thermal insulation of refrigerant pipe
Be sure to give insulation work to refrigerant pipe by covering liquid pipe and gas pipe separately
with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint
between indoor unit and insulating material, and insulating materials themselves. When insula-
tion work is insufficient, there is a possibility of condensation drip, etc. Pay special attention to
insulation work to ceiling plenum.