INSTALLATION OF OUTDOOR UNIT
11
ENGLISH
Piping length and the elevation
Floor Standing Air conditioner
• Do not use the pipe less than 5 m. Otherwise, it may cause damage of compressor and to
form dewdrop on the indoor unit. Also, it may cause to decrease capacity.
• Capacity is based on the length of 5 m and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
CAUTION
!
If installed tube is shorter than 5 m, additional charging is not necessary.
Additional Refrigerant = (A -5) x Additional refrigerant (g)
Model
Pipe Size mm(inch) Length A(m) Elevation B(m)
Additional refrigerant
(g/m)
Gas Liquid
Standard
Max.
Standard
Max.
APUW100LFT0
APUQ100LFT0
Ø 22.2 (7/8) Ø 9.52 (3/8)
550030 60