1
Press the mode button and the temperature
increasing button(▲) same time for three
seconds.
2
Set the volume of each fan speed(Low, Medium, Hi)
by using the temperature control button. Press the
fan speed button to select the fan speed.
The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP
function, it will be canceled. (The picture on the left
side is the example of setting the Hi wind to ESP
10.)
4
Press the mode button and the temperature
increasing button (▲) same time for three
seconds. Then the ESP setting will be activated
after the temperature display flashes three times.
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is
recommended that you should not use this function while using the remote controller.
EX)
❈ The E.S.P value is set at the proper value at the
factory. So it is highly recommended that you should
not change the E.S.P value at your discretion.
Static pressure(mmAq)
Setting value
01234
Model name
Step(H/M/L)
8.5 CMM(300cfm) 75 84 94 104 114
7.5 CMM(265cfm) 69 77 88 99
110
6.5 CMM(230cfm) 62 71 83 95
106
9.5 CMM(336cfm) 82 90 99 109
118
8.5 CMM(300cfm) 75 84 94 104
114
7.5 CMM(265cfm) 69 77 88 99
110
15 CMM(530cfm) 90 97 105 114
122
13.5 CMM(477cfm) 82 90 99 109 119
11.5 CMM(406cfm) 75 84 93 103
114
AMNW09GB1A0
[LMDN095HV]
AMNW12GB1A0
[LMDN125HV]
AMNW18GB2A0
[LMDN185HV]