EasyManua.ls Logo

LG MULTI V S ARUN048GSS4 - Selecting the Refrigerant Piping

LG MULTI V S ARUN048GSS4
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
MULTI V S System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
([DPSOH)LYHLQGRRUXQLWVFRQQHFWHG
0XOWL962XWGRRU8QLW
IDU: Indoor Units.
$0DLQ3LSHIURP0XOWL962XWGRRU8QLWWR
Y-branches.
B: Branch Piping.
C: Branch Piping to Indoor Unit (IDU).
Selecting the Refrigerant Piping
Indoor units should be installed at a lower
position than the Header.
Y-branch pipes cannot be used after
Headers.
Install the Header so that the pipe dis-
tances between the between the con-
QHFWHG LQGRRU XQLWV DUH PLQLPL]HG /DUJH
differences in pipe distances can cause in-
door unit performances to fluctuate.
$OZD\VUHIHUHQFHWKH/$760XOWL9VRIWZDUH
report.
0XOWL962XWGRRU8QLW&DSDFLW\WRQ /LTXLGSLSHLQFKHV2' 9DSRUSLSHLQFKHV2'
3.0 Ø3/8 Ø5/8
4.0 Ø3/8 Ø5/8
4.4 Ø3/8 Ø3/4
'RZQVWUHDP7RWDO&DSDFLW\RI,'8V%WXK
1
/LTXLGSLSHLQFKHV2' 9DSRUSLSHLQFKHV2'
 Ø1/4 Ø1/2
 Ø3/8 Ø5/8
 Ø3/8 Ø3/4
Table 20: 6L]HRI0DLQ3LSH$)URP6SDFH,,8QLWWR<EUDQFKHV
Indoor Unit Capacity
1
/LTXLGSLSHLQFKHV2' 9DSRUSLSHLQFKHV2'
 1/4Ø 1/2Ø
 3/8Ø 5/8Ø
 3/8Ø 3/4Ø
1
9,600-24,200 Btu/h 4-way 3 feet x 3 feet Cassette and 15,400-24,200 Btu/h High Static Ducted indoor units have Ø3/8 (liquid) and Ø5/8 (vapor).
Table 21: Size of Branch Piping (B) to Branch Piping (B).
Table 22: Size of Branch Piping to Indoor Unit (C).
1
9,600-24,200 Btu/h 4-way 3 feet x 3 feet Cassette and 15,400-24,200 Btu/h High Static Ducted indoor units have Ø3/8 (liquid) and Ø5/8 (vapor).
Vapor Pipe
Main Pipe
Liquid Pipe
Branch Piping
IDU
IDUIDUIDU
C
IDU
IDU
IDU
CCC
CCC