PRDCAM AHU Communication Kit Installation Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Controller Settings
AHU COMMUNICATIONS KIT INSTALLATION
Note : Dip SW 1-2 is for contact signal control
Note : Maintain previous value when getting intermediate value to UI4
Name Port
Value
Electrical
Spec.
Function
Short Open
On / Off UI1 (DI) On Off Non voltage Operation On/Off Control
Cool / Heat UI2 (DI) Heating Cooling Non voltage
Heating/Cooling Operation Control
if operation mode (DIP SW 3-2, 3-3) is set to cooling only mode, UI2
“Short” status will work as fan mode.
if operation mode (DIP SW 3-2, 3-3) is set to heating only mode, UI2
“Open” status will work as fan mode.
Forced
Thermo
On / Off
UI3 (DI)
Thermal
On
Thermal
Off
Non voltage
When UI4(Target temp.) is less than 1.5 V, Target temp. and Room
temp. is fixed like below table
Target
Temp.
UI4 (AI)
Voltage
Electrical
Spec.
Cooling Mode (°F)
V Min. Max
< 1.5 0 1.6
DC 0~10 V,
20 mA
UI3 short : 60
UI3 open : 80
UI3 short : 80
UI3 open : 60
06 061.29.10.2
26 266.24.25.2
46 461.39.20.3
66 666.34.35.3
86861.49.30.4
96 966.44.45.4
17 171.59.40.5
37376.54.55.5
57571.69.50.6
77776.64.65.6
87871.79.60.7
08086.74.75.7
28281.89.70.8
48486.84.85.8
68680.017.8 0.9
Mode
UI3 status
Thermal On
Target temp. = 60
Room temp. = 80
Target temp. = 80
Room temp. = 60
Thermal Off
Target temp. = 80
Room temp. = 60
Target temp. = 60
Room temp. = 80
Heating Mode (°F)
Cooling Mode (°F) Heating Mode (°F)
Universal Input UI Setting #1
UI setting #1 is available when DIP switches SW1-2, SW2-3, and SW2-4 are Off.