45
Installation
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Specifications
Table 13: EEV Kit Specications Table.
EEV Kit Design Parameters
Maximum of one (1) EEV Kit can be connected to one (1) AHU
Communications Kit.
Minimum coil entering air temperature for heating mode is 41°F.
Requires field-supplied six-conductor communication cable to
connect to AHU Communications Kit.
Maximum distance between EEV Kit and AHU Communications Kit
is thirty-two (32) feet.
Designed for indoor installations (field-supplied waterproof enclo-
sure must be used when installing outdoors).
Figure 16: EEV Kit.
EEV KIT INSTALLATION
Introduction, Specications, and Design Parameters
Introduction
When used with the LG AHU Communications Kit (sold separately), the LG EEV Kit controls refrigerant flow between
LG Multi V air-source or water-source units and a third-party air handler unit (AHU).
The EEV Kits for PAHCMS000 are offered in four sizes:
PRLK048A0 supports 12 through 96 MBH (8 tons maximum)
PRLK096A0 supports 96.1 through 192 MBH (16 tons maximum)
PRLK396A0 supports 192.1 MBH through 396 MBH (32 ton maximum)
PRLK594A0 supports 396.1 MBH through 594 MBH coils (48 ton maximum, requires EEV Controller
Module PAEEVA020).
Model Number
PRLK048A0
PRLK096A0
PRLK396A0
PRLK594A0
For Use With PAHCMR000 and PAHCMS000
PAHCMS000 with
EEV Controller
Module
PAEEVA020
Power Supply Requirements
Powered by Air Handler Unit Communicaons Kit (12 VDC)
Ambient Operang
Temperature Range
-4 to 149F
Ambient Operang
Humidity Range
0 to 98% (Non-condensing)
Dimensions (in., W x H x D) 8-5/8 x 15-15/16 x 3-5/16
13-25/32 x 7-
3/32 x 13-39/64
16-1/8 x 7-3/32 x
13-39/64
Net Weight (lbs.)
6.8
11.0
15.4
Shipping Weight (lbs.)
7.9
12.1
16.5
Maximum Air Handler Unit
Capacity (Btu/h)
96,000 192,000 396,000 594,000
Communicaons Cable
AWG 18 x 6 Stranded, Shielded Copper Wire
Refrigerant Type
R410A
Table 14: EEV Kit Compatibility Table.
PAHCMR000 PAHCMS000
PRLK048A0
(8 tons max)
HP/HR HP
PRLK096A0
(16 tons max)
HP HP
PRLK396A0
(32 tons max)
HP HP
PRLK594A0
(48 tons max)
NA
HP (requires EEV
module)
AHU Communicaon Kit
EEV Kit
HP = Heat Pump; HR = Heat Recovery