EasyManua.ls Logo

LG PAHCMS000 - PRLK396 A0 Wiring

LG PAHCMS000
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
PRDCAM AHU Communication Kit Installation Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
EEV KIT INSTALLATION
PRLK396A0 Wiring
Figure 26: PRLK396A0 EEV Kit Wiring.
Wiring Installation
1. Open the terminal box cover.
2. For PRLK396A0 / PRLK594A0, run the field-supplied wiring (six [6] wired, 18AWG, stranded, shielded copper) to / from the AHU Commu-
nications Kit through the cable connector on the EEV Kit.
3. Connect wiring to the terminal connections following the label and color codes pasted onto the bottom of the terminal box and shown
below. Securely tighten all connections.
4. Route the wiring through and out the EEV Kit as shown, and secure with the support tie (D).
5. Re-install the terminal box cover and secure the cover with the four (4) screws.
6. Taking care not to damage the field-supplied wiring or insulation, reattach the EEV Kit Top Panel by securing it with the screws at the four
(4) corners.
BR : Brown
RD : Red
BL : Blue
OR : Orange
YL : Yellow
WH : White
Field Wiring
A
B
PRLK396A0 EEV Kit
(cover removed)
10-3/4
7-1/2
Mounting
Hole 1/4
Pipe Outlet 5/8
to AHU coil liquid
pipe connection
Pipe Inlet 5/8
from ODU
D
D
AHU controller
Detail
A. Terminal Box Cover
B. Cable Strain Relief Connector
C. Terminal Connector
D. Electrical Wiring (field supplied,
6 wires, 18 AWG, stranded,
shielded
Figure 27: PRLK594A0 EEV Kit Wiring.
A
B
PRLK594A0 EEV Kit
(cover removed)
AHU controller
AHU EEV controller
(sold separately)
D
Detail
B
R
R
D
B
L
O
R
Y
L
W
H
EEV
BR: Brown
RD: Red
BL: Blue
OR: Orange
YL: Yellow
WH: White
C
9-7/8
Mounting
Hole 1/4”
Pipe Outlet 5/8
to AHU coil liquid
pipe connection
Pipe Inlet 5/8
from ODU
A. Terminal Box Cover
B. Cable Strain Relief Connector
C. Terminal Connector
D. Electrical Wiring (field supplied,
6 wires, 18 AWG, stranded,
shielded
10-3/4
D
scale : inch
D
BR : Brown
RD : Red
BL : Blue
OR : Orange
YL : Yellow
WH : White
Field Wiring

Other manuals for LG PAHCMS000

Related product manuals