EasyManuals Logo

LG Single "A" User Manual

LG Single "A"
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
- 62 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 3 Control logic
Low ambient cooling: In this situation outdoor fan works in ON/OFF control.
If the pipe temperature is 0~10C and it is falling rapidly in that case compressor will run for 5 min & then it will go in low
ambient control.
After the system is stopped by CT cut or heat sink cut-off, cycle will return to the normal operating control.
T pipe (Cond Out)
Outdoor fan Setting value
Setting value
Off Off
T2 :10(Option)˚C
T1 :4(Option)˚C

Table of Contents

Other manuals for LG Single "A"

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Single "A" and is the answer not in the manual?

LG Single "A" Specifications

General IconGeneral
BrandLG
ModelSingle "A"
CategoryAir Conditioner
LanguageEnglish

Related product manuals